PVI Industries Water Heater PV 6319 User Manual

SPECIFICATION FOR DOMESTIC WATER HEATERS  
Condensing, Low NOx, Gas-Fired Water Heaters with Nickel-Plated Storage Tanks  
Furnish and install POWER VT condensing gas water heater(s) as manufactured by PVI Industries, LLC  
of Fort Worth, Texas. Supply in quantities and model numbers as indicated on the plumbing schedule.  
Emissions  
NOx emissions will not exceed 30 ppm when corrected to 3% O2 (for inputs greater than 399,000 Btu).  
NOx emissions will not exceed 55 ppm when corrected to 3% O2 (for 399,000 Btu input). These levels will be  
certified by independent agency.  
Gas and Electrical Consumption  
The water heater will operate at a minimum of 94% thermal efficiency when tested to ANSI Z21.10.3. The water  
heater will comply with paragraph 7.2.4.4, the thermal efficiency, the standby loss, and all other requirements of  
ASHRAE 90.1-1999.  
Pressure Vessel and Heating Surfaces  
The water heater will be a vertical fire tube design that is constructed and stamped in accordance with Section IV,  
Part HLW of the ASME code. Both the storage and heating sections of the water heater will be National Board  
Registered for a working pressure of 150 psi and will be pressure tested at 1-1/2 times working pressure. The fireside of  
the heating surfaces will be of boiler-grade steel. The waterside of the heating tubes will be sealed in copper. The  
heating tubes will be rolled, beaded, and seal welded into the tube sheets. The combustion side of the tube sheet will be  
insulated by a layer of ceramic fiber that will protect the tube sheet from both thermal stresses and failure that can result  
from the accumulation of scale and precipitants.  
Lining  
The tank will be a plated with electroless nickel (EN). Plating will occur after the pressure vessel is completely  
fabricated and all welding is completed. The EN plating will be a high-phosphorus (10%) and nonporous composition  
suitable for submersion service (ASTM B733 standard may be used as a guideline). The finished lining will not require  
sacrificial anode rods. For additional protection against galvanic corrosion, which may occur within the potable water  
system, the EN plating may have a high-dielectric-strength polymer overcoat.  
Burner and Venting  
Combustion will be provided by an induced-draft power burner with a gas train meeting the following agency  
requirement for the input specified:  
___ UL (standard)  
___ FM  
___ IRI  
___ Other ______________________  
Water heater will be a category IV, condensing appliance, UL listed for use with CPVC vent or AL 29-4C stainless  
steel vent. Burner will be configured to accept ____ room air _____ direct inlet combustion air. Water heater will operate  
with a minimum gas pressure of 4-½ inches water column.  
(continued)  
PV 6319 4/04  
1
 

Peavey Musical Instrument Amplifier 112E User Manual
Pfaff Sewing Machine 489 User Manual
Phase Technology Speaker SM500i User Manual
Philips Digital Photo Frame VR 700 User Manual
Philips MP3 Docking Station AJ300D 12 User Manual
Philips Projector Accessories BDL425IV User Manual
Poulan Lawn Mower 188870 User Manual
Poulan Lawn Mower PR20H42STB User Manual
Praktica Digital Camera D00397 User Manual
Presto Coffeemaker 09401 User Manual